Product Description
Specifications:150 Amps, 3 Pole, Bolt-On, Thermal Magnetic Approval UL Mfg. Status: Obsolete, Residential/Commercial FXD63L150L, UPC#78364300619 adjustable trip, magnetic, molded case, fd frame, 600 VAC, 250 VDC, 150 ampere, 3 pole, trip setting 400 to 800 ampere, motor fla 30.76 to 74.50 ampere, terminal line lug, load lug, 6 awg to 350 kcmil copper/4 awg to 350 kcmil aluminum wire, fxd6 models are to be used in conjunction with motor-running, over-current-protection devices and should permit the motor to start without nuisance tripping form motor-inrush current. ETI Breaker do not provide thermal over load protection.