Product Description
MGA36500
I-Line 3 Pole 500 Amp, 240/480/600 VAC at 50/60 HZ, 480 VAC star/277 VAC at 50/60 HZ, 600 VAC star/347 VAC at 50/60 HZ (Underwriters Lab/CSA/nom), 240/415 VAC at 50/60 HZ (iec), 450 ampere, 3 pole, interrupting rating 65 kiloampere at 240 VAC, 35 kiloampere at 480 VAC or 480 VAC star/277 VAC, 18 kiloampere at 600 VAC or 600 VAC star/347 VAC (Underwriters Lab/CSA/nom), 35 kiloampere at 415 VAC, 50 kiloampere at 240 VAC (iec), trip setting 1600 to 8000 Ampere, application power distribution, used on class 612/661 i-line[r] panel board/switchboard, approval Underwriters Lab, CSA, powerpact[r] brand, mg model, frame type m, size 8.27 inch w x 8.05 inch d x 12.86 inch h, terminal wire size 3 to 3/0 awg to 500 kcmil (aluminum/copper). Made in three AIC rating groups, MGA=35k, MJA=65k and MLA=100k.Square D Schneider Electric. Products available through www.breakeroutlet.com on eBay.