Product Description
HFD2030
- Eaton Cutler-Hammer OEM
- Series C MCCB
- Panel mount
- 30 Ampere
- 2 Pole
- 65k rated @ 480VAC
- 600 VAC
- Thermal Magnetic Trip
- Fixed Trip
- Approval UL, CSA. CE
- Mfg Status: Available
- Industrial
- New or Re-certified
HFD2030 Molded case, thermal magnetic, F frame Circuit Breaker, 600 VAC at 50/60 Hz, 250 VDC, 40 Deg c, HFD2030L, 2 pole, interrupting rating 100 kiloampere at 240 vac, 65 kiloampere at 480 vac, 25 kiloampere at 600 vac, 22 kiloampere at 250 VDC (ul), 100 kiloampere at 220/240 VAC, 65 kiloampere at 380/415/440 vac, 25 kiloampere at 500 VAC, 22 kiloampere at 250 VDC (IEC), terminal standard pressure line terminal, standard pressure load terminal, size 4.125 inch w x 3.375 inch d x 6 inch h, approval Underwriters Laboratories, HFD model, applicable standard IEC 157-1. Suitable for 2 Pole applications, use outside poles (single phase). The Family of circuit breakers includes: 1. Themral-MagneticTrip Breakers. 2.Electronic RMS Trip Breakers. 3. Molded Case Switches. 4. Motor Circuit Protectors. 5. Current Limiting Breakers. 6. Special Application Breakers. 7. World Breakers. 8. Marine applications. 9. Moisture-Fungus Proof Treatment. For 50 degree calibration designate or add suffix V.